To protect the roof from damaging
ultraviolet rays, which cause it to dry, shrink, and eventually crack,
the roof surfacing is usually treated in several ways. A common application
is to spread gravel onto a layer of asphalt. This aggregate surfacing,
as it is known, helps protect the roof not only from the elements but
also from punctures and other penetrations.
Another way to protect the top layer is with a mineral-surfaced cap sheet,
a membrane with granular bits embedded on the top side that gives the
roof a slightly textured surface. A mineral cap sheet’s relatively
smoother surface, compared to gravel, makes it easier to inspect for things
like nails or broken glass, but at the same time it also makes it more
vulnerable to punctures from such debris.
A third method of treating the top layer of a built-up roof is to apply
an aluminum-based reflective coating. The coating reflects sunlight, thereby
keeping the roof from getting too hot and lessening damage from ultraviolet
rays. One drawback with this surface is that it needs to be painted every
five to seven years to maintain its reflective qualities.
Modified Bitumen Systems
In a second type of roofing system, called modified bitumen, typically
two layers of roofing membrane are laid down: the bottom one has a smooth
surface while the top one is embedded with a mineral surface, creating
an effect similar to the multiple membranes of a built-up roof.
The layers in a modified bitumen system can be applied two ways: In the
first method, known as APP (atactic propylene), a torch is used to heat
the asphalt pre-applied to the bottom of the felt, adhering the membrane
to the layer below. In the SBS (styrene butadiene styrene) method, the
mineral cap sheet is usually hot mopped over the smooth-surfaced first
layer, or in some cases, torched down as in an APP system.
Cold-applied Systems
The third major type of roofing system also uses fiber-reinforced bituminous
membranes. Instead of asphalt, however, a liquid adhesive and a catalyst
are mixed in a cold solution and applied to the surface to promote adhesion.
An increasingly popular type of cold-applied system uses self-adhesive
roofing membranes. As with the modified bitumen systems, a bottom layer
with a smooth surface is used with a mineral cap sheet on top. Instead
of hot mopping asphalt or torching the layers down, however, the self-adhesive
membranes come with their own pre-applied adhesive elements and are directly
applied to the substrate using primer.
In a second kind of cold-applied system, a waterproofing liquid is distributed
onto the roof deck and a reinforcing fleece membrane is rolled over it.
The fleece absorbs the underlying liquid, adhering to the deck and forming
a seamless layer. Additional layers are applied in the same way. Sand
can be spread into the top layer to achieve a gritty finish if desired.
Single-ply roofing systems—i.e., those with only one membrane instead
of multiple layers—are also sometimes used, especially in new commercial
construction. These types of roofs do not offer the durability or consistency
of either the built-up, modified bitumen, or cold-applied systems, so
they are not recommended for multi-family buildings.
Wood Deck Considerations
One limitation with built-up roof systems comes into play with wood roof
decks, such as in your building. Applying hot-mopped asphalt requires
heating it in a kettle at approximately 400° F. The New York Fire
Department regulations, however, prohibit open flames on any roof with
a wood deck. These regulations similarly rule out using the torch-down
method for applying membranes.
As an alternative, the asphalt is heated in a kettle on the ground level
of the building and pumped up to the roof. This method, however, can be
used only for buildings approximately six stories or lower because of
the logistics of pumping a piping-hot material alongside a building. The
temperature of the asphalt, for example, cannot fluctuate too much from
the time it is heated in the kettle to when it reaches the roof. Another
problem with placing the kettle on the ground is that asphalt gives off
potentially hazardous fumes, inviting fines from the city’s Department
of Environmental Protection. In such cases, a low-fuming type of asphalt
should be used along with additional fume-lowering methods.
For buildings with wood roof decks, which require pumping the asphalt
up, or buildings with concrete terrace decks where hoisting a kettle of
hot asphalt is impractical (such as on a tall building with a series of
set-back roofs or terraces), a cold-applied roofing system may be more
feasible.
Whether the adhesive being used in a roof replacement is hot asphalt
or one of the cold solutions, the material is sensitive to heat, humidity,
and how it is applied. Asphalt that is too hot or cold, or spread too
quickly or slowly, will not adhere properly, resulting in gaps and blistering
in the membranes. Hiring a contractor with experienced, well-trained workers
who carefully follow specifications from the manufacturer and engineer
is critical.
Warranties
Whatever type of roof your cooperative decides to install, you should
request what is called a “No Dollar Limit” warranty. Standard
warranties cover only defects in the roofing materials on a pro-rated
basis, diminishing in value as the years pass, and they won’t pay
for shoddy installation. NDL warranties, on the other hand, will reimburse
for the full cost of replacing the roof for both defective materials and
substandard workmanship, even if the system fails in the last year of
the warranty. NDL warranties typically come in 15- or 20-year terms. Expect
to pay approximately $17 to $20 a square foot to replace a standard roof,
which includes demolition and disposal of existing roofing materials and
asbestos containing debris, installation of new materials, labor, and
an NDL warranty. (Independent engineering consulting fees would be separate.)
During the design phase, tests will need to be conducted to determine
if any of the roofing materials contain asbestos. The presence of asbestos
will require licensed asbestos workers to dispose of the material in an
approved landfill facility.
Maintenance and Care
A newly replaced roof will eventually be compromised if not maintained
and cared for. The building’s staff should regularly inspect the
roof for damaging items such as debris and sharp objects (nails, glass,
pieces of metal), clogged drains, faulty pitch pans, and defective flashing
and counterflashing (metal or other types of membranes used to cover the
intersections between the roof and chimneys and parapets). Pay special
attention to ponding on the roof, which could indicate that the roof is
not pitched at a sufficient enough angle to promote proper drainage. Using
a roof for recreational purposes not designed for such activities will
also shorten the roof’s longevity and weaken its waterproofing (and
possibly structural) capabilities.
A roof replacement program is a major capital investment, so a great
deal of care and consideration should go into selecting a qualified contractor
to perform the work. You would be well advised to engage an independent
engineering or architectural firm to prepare construction documents and
solicit at least four to six sealed bids from reputable roofing contractors.
The specification and bidding process will assure that the board receives
competitive pricing for the project and that the proper materials and
methods will be used.